Control of temperature, relative humidity and carbon dioxide for reduced ventilation in commercial otato storages

dc.contributor.authorIrvine, Douglas A.en_US
dc.date.accessioned2007-05-15T19:08:27Z
dc.date.available2007-05-15T19:08:27Z
dc.date.issued1997-09-01T00:00:00Zen_US
dc.degree.disciplineBiosystems Engineeringen_US
dc.degree.levelMaster of Science (M.Sc.)en_US
dc.description.abstractA microcomputer based monitoring and control system was designed, assembled, and field tested as a reduced ventilation controller in a commercial multi-bin potato storage in southern Manitoba to reduce energy consumption during winter months. The system was integrated with an automatic temperature controller to control the fresh air inlet, and used CO$\sb2$ and temperature as parameters for control of the fan operation in one of two 650 t bins monitored. The CO$\sb2$, temperature, and relative humidity as well as the fan status, and fan energy consumption were monitored in two adjacent 650 t potato storage bins. Potato storage facilities could reduce the demand for electrical power by turning ventilation off while emptying bins and grading potatoes for shipment during the months of December, January, and February. Monitored CO$\sb2$ concentrations increased quickly enough during any 8 to 10 h period, when all fans in the facility were simultaneously off, to warrant CO$\sb2$ set-point control to turn a fan on. Most times, the rapid removal of CO$\sb2$ from the test bin by the fan and continuous dilution from infiltration and exhaust with operation of fans in adjacent bins prevented the controlled fan from providing adequate ventilation when CO$\sb2$ was used as the only criterion for ventilation. The differential temperature between the upper and lower elevations of the potato piles were seen as a necessary criterion for ventilation when a bin ventilation fan remained off for an extended period and other fans were operating. A pre-set minimum differential temperature would also be the best criterion to turn fans off, rather than a lower CO$\sb2$ set point.en_US
dc.format.extent3457686 bytes
dc.format.extent184 bytes
dc.format.mimetypeapplication/pdf
dc.format.mimetypetext/plain
dc.identifier.urihttp://hdl.handle.net/1993/1296
dc.language.isoengen_US
dc.rightsopen accessen_US
dc.titleControl of temperature, relative humidity and carbon dioxide for reduced ventilation in commercial otato storagesen_US
dc.typemaster thesisen_US
Files
Original bundle
Now showing 1 - 1 of 1
Loading...
Thumbnail Image
Name:
mq23352.pdf
Size:
3.3 MB
Format:
Adobe Portable Document Format
Description:
License bundle
Now showing 1 - 1 of 1
Loading...
Thumbnail Image
Name:
license.txt
Size:
184 B
Format:
Plain Text
Description: